Standards of Practice

All of my Inspections are an unbiased, professional assessment of thousands of items that provides you with an expert opinion in report form on the condition of the physical structure and it's various systems. As a Professionally Licensed Real Estate Inspector, it is my job to address your concerns about any defective systems that could become costly surprises. I will gladly discuss remedies and repair recommendations for each specific situation.

In order to prepare the report, the inspector must conduct a visual and systems operation inspection of the property and components contained within. The inspection process typically takes at least 3 or more hours to complete. This of course will vary according to the size, condition, and age of the property. I strongly encourage you to accompany me during the inspection. This will give you a chance to ask questions and become familiar with the systems.

When your inspection is complete. You will receive a thorough written report accompanied by digital photographs. I will also discuss any routine maintenance tasks that are required to keep the home and its systems in top condition, as well as answer any questions you may have.

All of my Inspections are in compliance with the Texas Real Estate Commission (TREC) Standards of Practice. The Standards of Practice are the minimum levels of inspection practice required of inspectors for the accessible parts, components, and systems typically found in improvements to real property, excluding detached structures, decks, docks and fences. The inspector may provide a higher level of inspection performance than required by the standards of practice and may inspect parts, components, including detached structures, decks, docks, fences, and other systems in addition to those described by the standards of practice.

Please see the complete Texas Real Estate Commission Standards of Practice http://www.trec.state.tx.us/pdf/rules/535.227-233.pdf

Based on what is Present, Visible, and Accessible the Inspector will inspect the following items that may be included in your thorough inspection report:

  • (AFCI) ARC FAULT CIRCUIT INTERRUPTOR TESTING

  • AIR CONDITIONING, HEATING EQUIPMENT, VENTS, AND DUCTWORK 

  • ALARM SYSTEMS, SMOKE, FIRE, AND CARBON MONOXIDE DETECTION

  • ATTIC, STAIRS, INSULATION, VENTS, AND ASSOCIATED STRUCTURE SYSTEMS

  • BATHROOM FIXTURES, EXHAUST VENTS, AND HEATERS

  • CABINETS, COUNTER TOPS, AND CLOSETS

  • CRAWLSPACE, PIERS, BEAMS, GIRDERS, VENTS, AND SUBFLOOR STRUCTURES

  • DISHWASHER

  • DOOR BELL OR CHIME

  • EIFS: EXTERIOR INSULATED FINISH SYSTEMS 

  • ELECTRICAL SERVICE ENTRANCE, PANELS, AND BRANCH CIRCUITS

  • EXTERIOR WALLS, DOORS, SEALANTS, AND WEATHER STRIPPING

  • FIREPLACE, HEARTH, DAMPER, FLUE, CAP, AND ARRESTORS

  • FOOD WASTE DISPOSAL

  • FOUNDATION

  • FLOOR COVERINGS

  • GARAGE DOOR(S) AND OPENER(S) 

  • GAS LEAK DETECTION (TIF 8800) not matches or soap bubbles

  • GAS SUPPLY SYSTEM FROM METER TO APPLIANCES

  • (GFCI) GROUND FAULT CIRCUIT INTERRUPTOR TESTING

  • GRADING, DRAINAGE, GUTTER, AND DOWNSPOUTS

  • HYDROTHERAPY TUB & EQUIPMENT   

  • INTERIOR WALLS, DOORS, CEILINGS, AND FLOORS

  • LANDSCAPING EFFECTS ON STRUCTURE

  • LAWN AND GARDEN SPRINKLER SYSTEMS

  • MICROWAVE

  • OVEN, COOKTOP, AND RANGE

  • OTHER INSTALLED KITCHEN APPLIANCES

  • OUTDOOR COOKING EQUIPMENT

  • PLUMBING SUPPLY, DRAINS, WASTE, AND VENTS

  • PORCHES, DECKS, BALCONIES, STAIRS, AND HANDRAILS

  • RANGE HOOD AND EXHAUST VENT 

  • ROOF COVERING, FLASHINGS, AND ROOF STRUCTURE

  • SEPTIC SYSTEMS

  • STORAGE BUILDINGS WITH UTILITIES

  • SWIMMING POOL, HOT TUB, SECURITY, AND ASSOCIATED EQUIPMENT 

  • TRASH COMPACTOR

  • WATER HEATER 

  • WELLS

  • WINDOWS, SCREENS, LINTELS, FLASHING, AND DOOR GLAZING

  • WHOLE HOUSE VACUUM SYSTEMS

  • WOOD DESTROYING INSECTS AND MICROBIAL ORGANISMS

  • Additional items and systems unique to a particular property can also be inspected

    §535.227. Standards of Practice: General Provisions

    (a)     Definitions.

    (1)                                    Accessible In the reasonable judgment of the inspector, capable of being approached, entered, or viewed without:

    (A)                undue hazard to the inspector;

    (B)                moving furnishings or large, heavy, or fragile objects;

    (C)                using specialized tools or procedures;

    (D)                disassembling items other than covers or panels intended to be removed for inspection;

    (E)                                  damaging property; or

    (F)                                   using a ladder for portions of the inspection other than the roof or attic space

    (2)                 Chapter 1102 – Texas Occupations Code, Chapter 1102

    (3)                 Cosmetic – Related only to appearance or aesthetics, and not related to structural performance, operability, or water penetration

    (4)                 Deficiency – A condition that, in the inspector’s reasonable opinion, adversely and materially affects the performance of a system or component or constitutes a hazard to life, limb, or property as specified by these standards of practice.  General deficiencies include but are not limited to inoperability, material distress, water penetration, damage, deterioration, missing parts, and unsuitable installation

    (5)                 Deficient – Reported as having one or more deficiencies

    (6)                 Inspect – To look at and examine accessible items, parts, systems, or components and report observed deficiencies

    (7)                 Performance – Achievement of an operation, function, or configuration consistent with accepted industry practice

    (8)                 Report – To provide the inspector's opinions and findings on the standard inspection report form

    (9)                 Specialized tools – Tools such as thermal imaging equipment, moisture meters, gas leak detection equipment, environmental testing equipment and devices, elevation determination devices, and ladders capable of reaching surfaces over one story above ground surfaces

    (10)             Specialized procedures – Procedures such as environmental testing, elevation measurement, and any method employing destructive testing that damages otherwise sound materials or finishes

    (11)             Standards of practice – §§535.227-535.233 of this title

     

    (b)                 Scope.

    (1)        These standards of practice define the minimum levels of inspection required for substantially completed residential improvements to real property up to four dwelling units.  A real estate inspection is a limited visual survey and basic operation of the systems and components of a building using normal controls and does not require the use of specialized tools or procedures.  The purpose of the inspection is to provide the client with information regarding the general condition of the residence at the time of inspection.  The inspector may provide a higher level of inspection performance than required by these standards of practice and may inspect parts, components, and systems in addition to those described by the standards of practice.


    (2)                 General Requirements.  The inspector shall:

    (A)                operate fixed or installed equipment and appliances listed herein in at least one mode with ordinary controls at typical settings;

    (B)                visually inspect accessible systems or components from near proximity to the systems and components, and from the interior of the attic and crawl spaces; and

    (C)                complete the standard inspection report form as required by §§535.222 and 535.223 of this title.

     

    (3)        General limitations.  The inspector is not required to:

    (A)        inspect:

    (i)                   items other than those listed herein;

    (ii)                 elevators;

    (iii)                detached structures, decks, docks, fences, or waterfront structures or equipment;

    (iv)                anything buried, hidden, latent, or concealed; or

    (v)                 automated or programmable control systems, automatic shut-off, photoelectric sensors, timers, clocks, metering devices, signal lights, lightning arrestor system, remote controls, security or data distribution systems, or solar panels;

    (B)        report:

    (i)                   past repairs that appear to be effective and workmanlike;

    (ii)                 cosmetic or aesthetic conditions; or

    (iii)                wear and tear from ordinary use;

    (C)        determine:

    (i)                   insurability, warrantability, suitability, adequacy, capacity, reliability, marketability, operating costs, recalls, counterfeit products, life expectancy, age, energy efficiency, vapor barriers, thermostatic operation, code compliance, utility sources, or manufacturer or regulatory requirements except as specifically required by these standards;

    (ii)                 the presence or absence of pests, termites, or other wood-destroying insects or organisms;

    (iii)                the presence, absence, or risk of asbestos, lead-based paint, mold, mildew, or any other environmental hazard, environmental pathogen, carcinogen, toxin, mycotoxin, pollutant, fungal presence or activity, or poison; or

    (iv)                types of wood or preservative treatment and fastener compatibility;

    (D)                anticipate future events or conditions, including but not limited to:

    (i)                   decay, deterioration, or damage that may occur after the inspection;

    (ii)                 deficiencies from abuse, misuse or lack of use,

    (iii)                changes in performance of any part, component, or system due to changes in use or occupancy;

    (iv)                the consequences of the inspection or its effects on current or future buyers and sellers;

    (v)                 common household accidents, personal injury, or death;

    (vi)                the presence of water penetration(s); or

    (vii)              future performance of any item;

    (E)        operate shut-off, safety, stop, pressure, or pressure-regulating valves or items requiring the use of codes, keys, combinations, or similar devices;

    (F)                designate conditions as safe;

    (G)               recommend or provide engineering, architectural, appraisal, mitigation, physical surveying, realty, or other specialist services;

    (H)                review historical records, installation instructions, repair plans, cost estimates, disclosure documents, or other reports;

    (I)                  verify sizing, efficiency, or adequacy of the ground surface drainage system;

    (J)                 operate recirculation or sump pumps;

    (K)                remedy conditions preventing inspection of any item;

    (L)                 apply open flame to operate any appliance;

    (M)               turn on decommissioned equipment, systems, or utility services; or

    (N)                provide repair cost estimates, recommendations, or re-inspection services.

    (4)                 In the event of a conflict between specific provisions and general provisions in the standards of practice, specific provisions shall take precedence.

     

    (5)     Departure.

    (A)        An inspector may depart from the standards of practice only if the requirements of subparagraph (B) are met, and:

    (i)                   the inspector and client agree the item is not to be inspected;

    (ii)                 the inspector is not qualified to inspect the item;

    (iii)                conditions beyond the control of the inspector reasonably prevent inspection of an item;

    (iv)                the item is a common element of a multi-family development and is not in physical contact with the unit being inspected, such as the foundation under another building or a part of the foundation under another unit in the same building;

    (v)                 the inspector reasonably determines that conditions or materials are hazardous to the health or safety of the inspector; or

    (vi)                the inspector reasonably determines that actions of the inspector may cause damage to the property.

    (B)        If a part, component, or system required for inspection is not inspected, the inspector shall:

    (i)                   advise the client at the earliest practical opportunity that the part, component, or system will not be inspected; and

    (ii)                 make an appropriate notation on the inspection report form, clearly stating the reason the part, component, or system was not inspected.

    (C)        If the inspector routinely departs from inspection of a part, system, or component, the earliest practical opportunity for the notice required by this subsection is the first contact with the prospect and the inspector has reason to believe that the property being inspected has the part, system, or component the inspector routinely does not inspect.

     

    (c)                 Enforcement.  Failure to comply with the standards of practice is grounds for disciplinary action as prescribed by Chapter 1102.

     

     


    §535.228. Standards of Practice: Minimum Inspection Requirements for Structural Systems

    (a)        Foundations.  The inspector shall:

    (1)        inspect slab surfaces, foundation framing components, subflooring, and related structural components;

    (2)        report:

    (A)        the type of foundation(s); and

    (B)        the vantage point from which the crawl space was inspected; and

    (3)        generally report present and visible indications used to render the opinion of adverse performance, such as:

    (A)                open or offset concrete cracks;

    (B)                binding, out-of-square, non-latching, warped, or twisted doors or frames;

    (C)                framing or frieze board separations;

    (D)                out-of-square wall openings or separations at wall openings or between the cladding and window/door frames;

    (E)                sloping floors, countertops, cabinet doors, or window/door casings;

    (F)                wall, floor, or ceiling cracks;

    (G)               rotating, buckling, cracking, or deflecting masonry cladding;

    (H)                separation of walls from ceilings or floors; and

    (I)                  soil erosion, subsidence or shrinkage adjacent to the foundation and differential movement of abutting flatwork such as walkways, driveways, and patios;

    (4)         report as Deficient:

    (A)                exposed or damaged reinforcement;

    (B)                a crawl space that does not appear to be adequately ventilated;

    (C)                crawl space drainage that does not appear to be adequate;

    (D)                deteriorated materials;

    (E)                damaged beams, joists, bridging, blocking, piers, posts, pilings, or subfloor;

    (F)                non-supporting piers, posts, pilings, columns, beams, sills, or joists; and

    (G)               damaged retaining walls related to foundation performance; and

    (5)         render a written opinion as to the performance of the foundation.

    (b)                Specific limitations for foundations.  The inspector is not required to:

    (1)                 enter a crawlspace or any area where headroom is less than 18 inches or the access opening is less than 24 inches wide and 18 inches high;

    (2)                 provide an exhaustive list of indicators of possible adverse performance; or

    (3)                 inspect retaining walls not related to foundation performance.

     

    (c)                 Grading and drainage.  The inspector shall report as Deficient:

    (1)                 improper or inadequate grading around the foundation (including flatwork);

    (2)                 erosion;

    (3)                 water ponding; and

    (4)                 deficiencies in installed gutter and downspout systems.

    (d)                 Specific limitations for grading and drainage.  The inspector is not required to:

    (1)                 inspect flatwork or detention/retention ponds (except as related to slope and drainage);

    (2)                 determine area hydrology or the presence of underground water; or

    (3)                 determine the efficiency or operation of underground or surface drainage systems.


    (e)                 Roof covering materials.  The inspector shall:

    (1)                 inspect the roof covering materials from the surface of the roof;

    (2)                 report:

    (A)                type of roof covering(s);

    (B)                vantage point from where the roof was inspected

    (C)                any levels or surfaces that were not accessed;

    (D)                evidence of previous repairs to roof covering materials, flashing details, skylights, and other roof penetrations; and

    (E)                evidence of water penetration; and

    (3)                 report as Deficient:

    (A)                a roof covering that is not appropriate for the slope of the roof;

    (B)                deficiencies in:

    (i)                   fastening of roof covering material, as determined by a random sampling;

    (ii)                 roof covering materials;

    (iii)                flashing details;

    (iv)                skylights; and

    (v)                 other roof penetrations.

    (f)         Specific limitations for roof covering.  The inspector is not required to:

    (1)                 determine the remaining life expectancy of the roof covering;

    (2)                 inspect the roof from the roof level if, in the inspector’s reasonable judgment, the inspector cannot safely reach or stay on the roof or significant damage to the roof covering materials may result from walking on the roof;

    (3)                 determine the number of layers of roof covering material;

    (4)                 identify latent hail damage; or

    (5)                 provide an exhaustive list of locations of water penetrations or previous repairs.

     

    (g)                 Roof structure and attic.  The inspector shall:

    (1)                 report:

    (A)                the vantage point from which the attic space was inspected;

    (B)                the presence of and approximate average depth of attic insulation and thickness of vertical insulation, when visible; and

    (C)                evidence of water penetration; and

    (2)                 report as Deficient:

    (A)               attic space that does not appear to be adequately ventilated;

    (B)               deficiencies in installed framing members and decking;

    (C)               deflections or depressions in the roof surface as related to the adverse performance of the framing and the roof deck;

    (D)               missing insulation;

    (E)               deficiencies in attic access ladder and access opening; and

    (F)                deficiencies in attic ventilators.

    (h)                 Specific limitations for roof structure and attic. The inspector is not required to:

    (1)                 enter attics or unfinished spaces where openings are less than 22 inches by 30 inches or headroom is less than 30 inches;

    (2)                 operate powered ventilators; or

    (3)                 provide an exhaustive list of locations of water penetrations.


    (i)                   Interior walls, ceilings, floors, and doors. The inspector shall:

    (1)                 report evidence of water penetration; and

    (2)                 report as Deficient:

    (A)               doors and hardware that do not operate properly;

    (B)               deficiencies related to structural performance or water penetration; and

    (C)               lack of fire separation between the garage and the residence and its attic space.

    (j)                   Specific limitation for interior walls, doors, ceilings, and floors.  The inspector is not required to:

    (1)                 report cosmetic damage or the condition of floor, wall, or ceiling coverings; paints, stains, or other surface coatings; cabinets; or countertops, or

    (2)                 provide an exhaustive list of locations of water penetrations.

     

    (k)                Exterior walls, doors, and windows.  The inspector shall:

    (1)                 report evidence of water penetration; and

    (2)                 report as Deficient:

    (A)               the lack of functional emergency escape and rescue openings in all sleeping rooms;

    (B)               the lack of a solid wood door not less than 1-3/8 inches in thickness, a solid or honeycomb core steel door not less than 1-3/8 inches thick, or a 20-minute fire-rated door between the residence and an attached garage;

    (C)               missing or damaged screens;

    (D)               deficiencies related to structural performance or water penetration; and

    (E)               deficiencies in:

    (i)                   claddings;

    (ii)                 water resistant materials and coatings;

    (iii)                flashing details and terminations;

    (iv)                the condition and operation of exterior doors, garage doors, and hardware; and

    (v)                 window operation and components.

    (l)                   Specific limitations for exterior walls, doors, and windows.  The inspector is not required to:

    (1)                 report the condition or presence of awnings, shutters, security devices, or systems;

    (2)                 determine the cosmetic condition of paints, stains, or other surface coatings; or

    (3)                 operate a lock if the key is not available.

     

    (m)               Exterior and interior glazing.  The inspector shall:

    (1)                 inspect the window and door glazing; and

    (2)                 report as Deficient:

    (A)                insulated windows that are obviously fogged or display other evidence of broken seals;

    (B)                deficiencies in glazing, weather stripping, and glazing compound in windows and exterior doors; and

    (C)                the absence of safety glass in hazardous locations.

    (n)        Specific limitation for exterior and interior glazing.  The inspector is not required to:

    (1)                 exhaustively observe insulated windows for evidence of broken seals;

    (2)                 exhaustively observe glazing for identifying labels; or

    (3)                 identify specific locations of damage.


    (o)        Interior and exterior stairways.  The inspector shall report as Deficient:

    (1)                 spacing between intermediate balusters, spindles, or rails for steps, stairways, guards, and railings that permit passage of an object greater than 4 inches in diameter, except that on the open side of the staircase treads, spheres less than 4-3/8 inches in diameter may pass through the guard rail balusters or spindles; and

    (2)                 deficiencies in steps, stairways, landings, guardrails, and handrails.

    (p)        Specific limitation for stairways.  The inspector is not required to exhaustively measure every stairway component.

     

    (q)        Fireplace and chimney.  The inspector shall report as Deficient:

    (1)                 built-up creosote in visible areas of the firebox and flue;

    (2)                 the presence of combustible materials in near proximity to the firebox opening;

    (3)                 the absence of fireblocking at the attic penetration of the chimney flue, where accessible;

    (4)                 an inoperative circulating fan; and

    (5)                 deficiencies in the:

    (A)                damper;

    (B)                lintel, hearth, hearth extension, and firebox;

    (C)                gas log lighter valve and location;

    (D)                combustion air vents; and

    (E)                chimney structure, termination, coping, crown, caps, and spark arrestor.

    (r)         Specific limitations for fireplace and chimney.  The inspector is not required to:

    (1)        verify the integrity of the flue;

    (2)        perform a chimney smoke test; or

    (3)        determine the adequacy of the draft.

     

    (s)         Porches, Balconies, Decks, and Carports.  The inspector shall:

    (1)                 inspect balconies, attached carports, and attached porches and abutting porches, decks, and balconies that are used for ingress and egress; and

    (2)                 report as Deficient:

    (A)                on decks 30 inches or higher above the adjacent grade, spacings between intermediate balusters, spindles, or rails that permit passage of an object greater than four inches in diameter;

    (B)                deficiencies in visible footings, piers, posts, pilings, beams, joists, decking, water proofing at interfaces, flashing, surface coverings, and attachment points of porches, decks, balconies, and carports; and

    (C)                deficiencies in, or absence of required, guardrails and handrails.

    (t)         Specific limitation for porches, balconies, decks, and carports.  The inspector is not required to:

    (1)         exhaustively measure the porch, balcony, deck, or attached carport components; or

    (2)         enter any area where headroom is less than 18 inches or the access opening is less than 24 inches wide and 18 inches high.

     


    §535.229. Standards of Practice: Minimum Inspection Requirements for Electrical Systems

    (a)        Service entrance and panels.  The inspector shall report as Deficient:

    (1)                 a drop, weatherhead, or mast that is not securely fastened to the structure;

    (2)                 the lack of a grounding electrode system;

    (3)                 the lack of a grounding electrode conductor;

    (4)                 the lack of a secure connection to the grounding electrode system;

    (5)                 deficiencies in the insulation of the service entrance conductors, drip loop, separation of conductors at weatherheads, and clearances;

    (6)                 electrical cabinets, gutters, meter cans, and panel boards that:

    (A)                are not secured to the structure;

    (B)                are not appropriate for their location;

    (C)                have deficiencies in clearances and accessibility;

    (D)                are missing knockouts; or

    (E)                are not bonded and grounded;

    (7)                 cabinets, disconnects, cutout boxes, and panel boards that do not have dead fronts secured in place with proper fasteners;

    (8)                 conductors not protected from the edges of electrical cabinets, gutters, or cutout boxes;

    (9)                 trip ties not installed on 240 volt circuits;

    (10)             deficiencies in the type and condition of the wiring in the cutout boxes, cabinets, or gutters;

    (11)             deficiencies in the compatibility of overcurrent devices and conductors;

    (12)             deficiencies in the overcurrent device and circuit for labeled and listed 240 volt appliances;

    (13)             a panel that is installed in a hazardous location, such as a clothes closet, a bathroom, where there are corrosive or easily ignitable materials, or where the panel is exposed to physical damage;

    (14)             the absence of appropriate connections, such as copper/aluminum-approved devices;

    (15)             the absence of anti-oxidants on aluminum conductor terminations;

    (16)             the lack of a main disconnecting means;

    (17)             the lack of arc-fault circuit interrupting devices serving family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreations rooms, closets, hallways, or similar rooms or areas; and

    (18)             failure of operation of installed arc-fault circuit interrupter devices.

    (b)        Specific limitations for service entrance and panels.  The inspector is not required to:

    (1)                 determine present or future sufficiency of service capacity amperage, voltage, or the capacity of the electrical system;

    (2)                 test arc-fault circuit interrupter devices when the property is occupied or damage to personal property may result, in the inspector’s reasonable judgment;

    (3)                 report the lack of arc-fault circuit interrupter protection when the circuits are in conduit;

    (4)                 conduct voltage drop calculations;

    (5)                 determine the accuracy of overcurrent device labeling;

    (6)                 remove covers where hazardous as judged by the inspector;

    (7)                 verify the effectiveness of overcurrent devices; or

    (8)                 operate overcurrent devices.


    (c)        Branch circuits, connected devices, and fixtures.  The inspector shall:

    (1)                 report the type of branch circuit conductors;

    (2)                 manually test the accessible smoke alarms by use of the manufacturer’s approved test or by the use of canned smoke; and

    (3)                 report as Deficient:

    (A)                the lack of ground-fault circuit interrupter protection in all:

    (i)                  bathroom receptacles;

    (ii)                 garage receptacles;

    (iii)               outdoor receptacles;

    (iv)               crawl space receptacles;

    (v)                 unfinished basement receptacles;

    (vi)               kitchen countertop receptacles; and

    (vii)              laundry, utility, and wet bar sink receptacles located within 6 feet of the outside edge of a laundry, utility, or wet bar sink; and

    (B)                the failure of operation of ground-fault circuit interrupter protection devices;

    (C)                receptacles that:

    (i)                   are damaged;

    (ii)                 are inoperative;

    (iii)                have incorrect polarity;

    (iv)                are not grounded, if applicable;

    (v)                 display evidence of arcing or excessive heat;

    (vi)                are not securely mounted; or

    (vii)              have missing or damaged covers;

    (D)                switches that:

    (i)                   are damaged;

    (ii)                 are inoperative;

    (iii)                display evidence of arcing or excessive heat;

    (iv)                are not securely mounted; or

    (v)                 have missing or damaged covers;

    (E)                deficiencies in or absences of conduit, where applicable;

    (F)                appliances and metal pipes that are not bonded or grounded;

    (G)               deficiencies in wiring, wiring terminations, junctions, junction boxes, devices, and fixtures, including improper location;

    (H)                the lack of equipment disconnects;

    (I)                  the absence of appropriate connections, such as copper/aluminum approved devices, if branch circuit aluminum conductors are discovered in the main or sub-panel based on a random sampling of accessible receptacles and switches;

    (J)                 improper use of extension cords;

    (K)                deficiencies in smoke alarms that are not connected to a central alarm system; and

    (L)                 the lack of smoke alarms:

    (i)                   in each sleeping room;

    (ii)                 outside each separate sleeping area in the immediate vicinity of the sleeping rooms; and

    (iii)                on each additional story of the dwelling, including basements but excluding crawl spaces and uninhabitable attics (in dwellings with split levels and without an intervening door between the levels, a smoke alarm installed on the upper level and the adjacent lower level shall suffice provided that the lower level is less than one full story below the upper level).

    (d)        Specific limitations for branch circuits, connected devices, and fixtures.  The inspector is not required to:

    (1)                 inspect low voltage wiring;

    (2)                 disassemble mechanical appliances;

    (3)                 verify the effectiveness of smoke alarms;

    (4)                 verify interconnectivity of smoke alarms

    (5)                 activate smoke alarms that are being actively monitored or require the  use of codes; or

    (6)                 verify that smoke alarms are suitable for the hearing-impaired.

     

    §535.230. Standards of Practice: Minimum Inspection Requirements for Heating, Ventilation, and Air Conditioning Systems

    (a)        Heating equipment.  The inspector shall:

    (1)                 report:

    (A)                the type of heating system(s); and

    (B)                the energy source(s);

    (2)                report as Deficient:

    (A)                an inoperative unit;

    (B)                deficiencies in the controls and operating components of the system;

    (C)                the lack of protection from physical damage;

    (D)                burners, burner ignition devices or heating elements, switches, and thermostats that are not a minimum of 18 inches above the lowest garage floor elevation, unless the unit is listed for garage floor installation;

    (E)                 inappropriate location;

    (F)                 inadequate access and clearances;

    (G)                deficiencies in mounting and operation of window units; and

    (H)                deficiencies in thermostats;

    (3)                 in electric units, report as Deficient deficiencies in:

    (A)                operation of heating elements; and

    (B)                condition of conductors; and

    (4)                 in gas units, report as Deficient:

    (A)                gas leaks;

    (B)                the presence of forced air in the burner compartment;

    (C)                flame impingement, uplifting flame, improper flame color, or excessive scale buildup;

    (D)                the lack of a gas shut-off valve; and

    (E)                deficiencies in:

    (i)                   conditioned, combustion, and dilution air;

    (ii)                 gas shut-off valves and locations;

    (iii)                gas connector materials and connections; and

    (iv)                the vent pipe, draft hood, draft, proximity to combustibles, and vent termination point and clearances.


    (b)        Cooling equipment other than evaporative coolers.  The inspector shall:

    (1)                 report the type of system(s); and

    (2)                 report as Deficient:

    (A)                inoperative unit(s);

    (B)                inadequate cooling as demonstrated by its performance in the reasonable judgment of the inspector;

    (C)                inadequate access and clearances;

    (D)                noticeable vibration of the blower fan or condensing fan;

    (E)                deficiencies in the condensate drain and auxiliary/secondary pan and drain system;

    (F)                water in the auxiliary/secondary drain pan;

    (G)               a primary drain pipe that terminates in a sewer vent;

    (H)                missing or deficient refrigerant pipe insulation;

    (I)                  dirty evaporator or condensing coils, where accessible;

    (J)                 damaged casings on the coils;

    (K)                a condensing unit lacking adequate clearances or air circulation or that has deficiencies in the condition of fins, location, levelness, or elevation above ground surfaces;

    (L)                 deficiencies in mounting and operation of window or wall units; and

    (M)               deficiencies in thermostats.

     

    (c)        Evaporative coolers.  The inspector shall:

    (1)                report:

    (A)              type of system(s) (one- or two-speed);

    (B)              the type of water supply line; and

    (C)              winterized units that are drained and shut down; and

    (2)                report as Deficient:

    (A)                inoperative units;

    (B)                inadequate access and clearances;

    (C)                corrosive and mineral build-up or rust damage/decay at the pump, louvered panels, water trays, exterior housing, or the roof frame;

    (D)                less than a one-inch air gap between the water discharge at the float and water level in the reservoir;

    (E)                corrosion, decay, or rust on the pulleys of the motor or blower;

    (F)                the lack of a damper; and

    (G)               deficiencies in the:

    (i)                   function of the pump;

    (ii)                 interior housing, the spider tubes, tube clips, bleeder system;

    (iii)                blower and bearings;

    (iv)                float bracket;

    (v)                 fan belt;

    (vi)                evaporative pad(s);

    (vii)              installation and condition of the legs on the roof rails and fasteners to the roof structure and  the unit;

    (viii)             roof jack; and

    (ix)                thermostats.


    (d)        Duct system, chases, and vents.  The inspector shall report as Deficient:

    (1)                 damaged ducting or insulation, improper material, or improper routing of ducts;

    (2)                 the absence of air flow at accessible supply registers in the habitable areas of the structure;

    (3)                 improper or inadequate clearance from the earth; and

    (4)                 deficiencies in:

    (A)                duct fans;

    (B)                filters;

    (C)                grills or registers;

    (D)                the location of return air openings; and

    (E)                gas piping, sewer vents, electrical wiring, or junction boxes in the duct system, plenum(s), and chase(s).

    (e)        Specific limitations for the heating equipment, cooling equipment, duct system, chases, and vents.  The inspector is not required to:

    (1)                 program digital thermostats or controls;

    (2)                 inspect:

    (A)               for pressure of the system refrigerant, type of refrigerant, or refrigerant leaks;

    (B)               winterized evaporative coolers; or

    (C)               humidifiers, dehumidifiers, air purifiers, motorized dampers, electronic air filters, multi-stage controllers, sequencers, heat reclaimers, wood burning stoves, boilers, oil-fired units, supplemental heating appliances, de-icing provisions, or reversing valves;

    (3)                operate:

    (A)                setback features on thermostats or controls;

    (B)                cooling equipment when the outdoor temperature is less than 60 degrees Fahrenheit;

    (C)                radiant heaters, steam heat systems, or unvented gas-fired heating appliances; or

    (D)                heat pumps when temperatures may damage equipment;

    (4)                verify:

    (A)              compatibility of components;

    (B)              the accuracy of thermostats; or

    (C)              the integrity of the heat exchanger; or

    (5)                 determine:

    (A)                sizing, efficiency, or adequacy of the system;

    (B)                uniformity of the supply of conditioned air to the various parts of the structure; or

    (C)                types of materials contained in insulation.

     

    §535.231. Standards of Practice: Minimum Inspection Requirements for Plumbing Systems

    (a)                 Plumbing systems.  The inspector shall:

    (1)                 report:

                                                     (A)               static water pressure;

                                                     (B)               location of water meter; and

                                                     (C)               location of main water supply valve; and

    (2)                 report as Deficient:

    (A)                the presence of active leaks;

    (B)                the lack of fixture shut-off valves;

    (C)                the lack of dielectric unions, when applicable;

    (D)                the lack of back-flow devices, anti-siphon devices, or air gaps at the flow end of fixtures;

    (E)                water pressure below 40 psi or above 80 psi static;

    (F)                the lack of a pressure reducing valve when the water pressure exceeds 80 PSI;

    (G)               the lack of an expansion tank at the water heater(s) when a pressure reducing valve is in place at the water supply line/system; and

    (H)                deficiencies in:

    (i)                   water supply pipes and waste pipes;

    (ii)                 the installation and termination of the vent system;

    (iii)                the operation of fixtures and faucets not connected to an appliance;

    (iv)                water supply, as determined by viewing functional flow in two fixtures operated simultaneously;

    (v)                 functional drainage at fixtures;

    (vi)                orientation of hot and cold faucets;

    (vii)              installed mechanical drain stops;

    (viii)             installation, condition, and operation of commodes;

    (ix)                fixtures, showers, tubs, and enclosures; and

    (x)                 the condition of the gas distribution system.

    (b)                Specific limitations for plumbing systems.  The inspector is not required to:

    (1)                 operate any main, branch, or shut-off valves;

    (2)                 operate or inspect sump pumps or waste ejector pumps;

    (3)                 inspect:

    (A)                any system that has been winterized, shut down or otherwise secured;

    (B)                circulating pumps, free-standing appliances, solar water heating systems, water-conditioning equipment, filter systems, water mains, private water supply systems, water wells, pressure tanks, sprinkler systems, swimming pools, or fire sprinkler systems;

    (C)                the inaccessible gas supply system for leaks;

    (D)                for sewer clean-outs; or

    (E)                for the presence or operation of private sewage disposal systems;

    (4)                 determine:

    (A)        quality, potability, or volume of the water supply; or

    (B)        effectiveness of backflow or anti-siphon devices; or

    (5)                 verify the functionality of clothes washing drains or floor drains.

     

    (c)                 Water heaters.  The inspector shall:

    (1)                 report the energy source;

    (2)                 report the capacity of the unit(s);

    (3)                 report as Deficient:

    (A)                inoperative unit(s);

    (B)                leaking or corroded fittings or tank(s);

    (C)                broken or missing parts or controls;

    (D)                the lack of a cold water shut-off valve;

    (E)                if applicable, the lack of a pan and drain system and the improper termination of the pan drain line;

    (F)                an unsafe location;

    (G)               burners, burner ignition devices or heating elements, switches, or thermostats that are not a minimum of 18 inches above the lowest garage floor elevation, unless the unit is listed for garage floor installation;

    (H)                inappropriate location;

    (I)                  inadequate access and clearances;

    (J)                 the lack of protection from physical damage;


    (K)                a temperature and pressure relief valve that:

    (i)                   does not operate manually;

    (ii)                 leaks;

    (iii)                is damaged;

    (iv)                cannot be tested due to obstructions;

    (v)                 is corroded; or

    (vi)                is improperly located; and

    (L)                 temperature and pressure relief valve discharge piping that:

    (i)                   lacks gravity drainage;

    (ii)                 is improperly sized;

    (iii)                has inadequate material; or

    (iv)                lacks proper termination;

    (4)                 in electric units, report as Deficient deficiencies in:

    (A)                operation of heating elements; and

    (B)                condition of conductors; and

    (5)                 in gas units, report as Deficient:

    (A)                gas leaks;

    (B)                lack of burner shield(s);

    (C)                flame impingement, uplifting flame, improper flame color, or excessive scale build-up;

    (D)                the lack of a gas shut-off valve; and

    (E)                deficiencies in:

    (i)                   combustion and dilution air;

    (ii)                 gas shut-off valve(s) and location(s);

    (iii)                gas connector materials and connections; and

    (iv)                vent pipe, draft hood, draft, proximity to combustibles, and vent termination point and clearances.

    (d)                 Specific limitations for water heaters.  The inspector is not required to:

    (1)                 verify the effectiveness of the temperature and pressure relief valve, discharge piping, or pan drain pipes;

    (2)                 operate the temperature and pressure relief valve if the operation of the valve may, in the inspector’s reasonable judgment, cause damage to persons or property; or

    (3)                 determine the efficiency or adequacy of the unit.

     

    (e)                 Hydro-massage therapy equipment.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s) and controls;

    (2)                 the presence of active leaks;

    (3)                 inaccessible pump(s) or motor(s);

    (4)                 the lack or failure of required ground-fault circuit interrupter protection; and

    (5)                 deficiencies in the ports, valves, grates, and covers.

    (f)                  Specific limitation for hydro-massage therapy equipment.  The inspector is not required to determine the adequacy of self-draining features of circulation systems.

     


    §535.232. Standards of Practice: Minimum Inspection Requirements for Appliances

    (a)        Dishwasher.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s);

    (2)                 rust on the interior of the cabinet or components;

    (3)                 failure to drain properly;

    (4)                 the presence of active water leaks; and

    (5)                 deficiencies in the:

    (A)                door gasket;

    (B)                control and control panels;

    (C)                dish racks;

    (D)                rollers;

    (E)                spray arms;

    (F)                operation of the soap dispenser;

    (G)               door springs;

    (H)                dryer element;

    (I)                  door latch and door disconnect;

    (J)                 rinse cap;

    (K)                secure mounting of the unit; and

    (L)                 backflow prevention.

     

    (b)        Food waste disposer.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s);

    (2)                 unusual sounds or vibration level;

    (3)                 the presence of active water leaks; and

    (4)                 deficiencies in the:

    (A)                splash guard;

    (B)                grinding components;

    (C)                exterior casing; and

    (D)                secure mounting of the unit.

     

    (c)        Range exhaust vent.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s);

    (2)                 a vent pipe that does not terminate outside the structure, if the unit is not of a re-circulating type or configuration;

    (3)                 inadequate vent pipe material;

    (4)                 unusual sounds or vibration levels from the blower fan(s);

    (5)                 blower(s) that do not operate at all speeds; and

    (6)                 deficiencies in the:

    (A)                filter;

    (B)                vent pipe;

    (C)                light and lens;

    (D)                secure mounting of the unit; and

    (E)                switches.

     

    (d)        Electric or gas ranges, cooktops, and ovens.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s);

    (2)                 the lack of a gas shut-off valve;

    (3)                 gas leaks; and

    (4)                 deficiencies in the:

    (A)                controls and control panels;

    (B)                thermostat(s) sensor support;

    (C)                glass panels;

    (D)                door gasket(s), hinges, springs, closure, and handles;

    (E)                door latch;

    (F)                heating elements or burners;

    (G)               thermostat accuracy (within 25 degrees at a setting of 350 °F);

    (H)                drip pans;

    (I)                  lights and lenses;

    (J)                 clearance to combustible material;

    (K)                anti-tip device;

    (L)                 gas shut-off valve(s) and location(s);

    (M)               gas connector materials and connections; and

    (N)                secure mounting of the unit.

     

    (e)        Microwave oven.  The inspector shall:

    (1)                 inspect built-in units; and

    (2)                 report as Deficient:

    (A)                inoperative unit(s); and

    (B)                deficiencies in the:

    (i)                   controls and control panels;

    (ii)                 handles;

    (iii)                the turn table;

    (iv)                interior surfaces;

    (v)                 door and door seal;

    (vi)                glass panels;

    (vii)              lights and lenses;

    (viii)             secure mounting of the unit; and

    (ix)                operation, as determined by heating a container of water or with other means of testing.

     

    (f)         Trash compactor.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s);

    (2)                 unusual sounds or vibration levels; and

    (3)                 deficiencies in the secure mounting of the unit.

     

    (g)        Mechanical exhaust vents and bathroom heaters.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s);

    (2)                 unusual sounds, speed, and vibration levels;

    (3)                 vent pipes that do not terminate outside the structure;

    (4)                 a gas heater that is not vented to the exterior of the structure; and

    (5)                 the lack of an exhaust ventilator in required areas.

     

    (h)        Garage door operators.  The inspector shall report as Deficient:

    (1)                 inoperative unit(s);

    (2)                   door locks or side ropes that have not been removed or disabled; and

    (3)                   deficiencies in:

    (A)                installation;

    (B)                condition and operation of the garage door operator;

    (C)                automatic reversal during the closing cycle;

    (D)                electronic sensors;

    (E)                the control button; and

    (F)                the emergency release components.

     

    (i)         Doorbell and chimes.  The inspector shall report as Deficient:

    (1)                 inoperable unit(s); and

    (2)                 deficiencies in components.

     

    (j)         Dryer vents.  The inspector shall report as Deficient:

    (1)                 improper routing and length of vent pipe;

    (2)                 inadequate vent pipe material;

    (3)                 improper termination;

    (4)                 the lack of a dryer vent system when provisions are present for a dryer; and

    (5)                 damaged or missing exterior cover.

     

    (k)        Specific limitations for appliances.  The inspector is not required to:

    (1)                 operate or determine the condition of other auxiliary components of inspected items;

    (2)                 test for microwave oven radiation leaks;

    (3)                 inspect self-cleaning functions;

    (4)                 test trash compactor ram pressure; or

    (5)                 determine the adequacy of venting systems.

     

    §535.233. Standards of Practice: Minimum Inspection Requirements for Optional Systems.  If an inspector agrees to inspect a component described in this section, §535.227 of this title relating to Standards of Practice: General Provisions and the applicable provisions below apply.

    (1)                 Lawn and garden sprinkler systems.  The inspector shall:

    (A)                manually operate all zones or stations on the system; and

    (B)                report as Deficient:

    (i)                   surface water leaks;

    (ii)                 the absence or improper installation of anti-siphon devices and backflow preventers;

    (iii)                the absence of shut-off valves;

    (iv)                deficiencies in water flow or pressure at the zone heads;

    (v)                 the lack of a rain or freeze sensor;

    (vi)                deficiencies in the condition of the control box; and

    (vii)              deficiencies in the operation of each zone, associated valves, and spray head patterns.

    (2)                 Specific limitations for lawn and garden sprinkler systems.  The inspector is not required to inspect:

    (A)                for effective coverage of the sprinkler system;

    (B)                the automatic function of the timer or control box;

    (C)                the effectiveness of the rain or freeze sensor; or

    (D)                sizing and effectiveness of anti-siphon devices or backflow preventers.

     

    (3)                 Swimming pools, spas, hot tubs, and equipment.  The inspector shall:

    (A)                report the type of construction;

    (B)                report as Deficient:

    (i)                   a pump motor, blower, or other electrical equipment that lacks bonding;

    (ii)                 the absence of or deficiencies in safety barriers;

    (iii)                water leaks in above-ground pipes and equipment;

    (iv)                deficiencies in lighting fixture(s);

    (v)                 the lack or failure of required ground-fault circuit interrupter protection; and

    (vi)                deficiencies in:

    (I)                  surfaces;

    (II)                tiles, coping, and decks;

    (III)              slides, steps, diving boards, handrails, and other equipment;

    (IV)              drains, skimmers, and valves; and

    (V)                filters, gauges, pumps, motors, controls, and sweeps; and

    (C)                when inspecting a pool heater, report deficiencies that these standards of practice require to be reported for the heating system.

     

    (4)                 Specific limitations for swimming pools, spas, hot tubs, and equipment.  The inspector is not required to:

    (A)                dismantle or otherwise open any components or lines;

    (B)                operate valves;

    (C)                uncover or excavate any lines or concealed components of the system or determine the presence of sub-surface leaks;

    (D)                fill the pool, spa, or hot tub with water;

    (E)                inspect any system that has been winterized, shut down, or otherwise secured;

    (F)                 determine the presence of sub-surface water tables; or

    (G)                inspect ancillary equipment such as computer controls, covers, chlorinators or other chemical dispensers, or water ionization devices or conditioners other than required by this section.

     

    (5)                 Outbuildings.  The inspector shall report as Deficient:

    (A)                the lack of ground-fault circuit interrupter protection in grade-level portions of unfinished accessory buildings used for storage or work areas, boathouses, and boat hoists; and

    (B)                deficiencies in the structural, electrical, plumbing, heating, ventilation, and cooling systems that these standards of practice require to be reported for the principal structure.

     

    (6)                 Outdoor cooking equipment.  The inspector shall:

    (A)                inspect the built-in equipment; and

    (B)                report the energy source; and

    (C)                report as Deficient:

    (i)                   inoperative unit(s);

    (ii)                 a unit or pedestal that is not stable;

    (iii)                gas leaks; and

    (iv)                deficiencies in:

    (I)                  operation;

    (II)                control knobs, handles, burner bars, grills, the box, the rotisserie (if present), and heat diffusion material;

    (III)              gas shut-off valve(s) and location(s); and

    (IV)              gas connector materials and connections.

     

    (7)                 Gas supply systems.  The inspector shall:

    (A)                test gas lines using a local or an industry-accepted procedure; and

    (B)                report as Deficient:

    (i)                   leaks; and

    (ii)                 deficiencies in the condition and type of gas piping, fittings, and valves.

    (8)                 Specific limitation for gas lines.  The inspector is not required to inspect sacrificial anode bonding or for its existence.


    (9)                 Private water wells.  The inspector shall:

    (A)                operate at least two fixtures simultaneously;

    (B)                recommend or arrange to have performed water quality or potability testing;

    (C)                report:

    (i)                   the type of pump and storage equipment; and

    (ii)                 the proximity of any known septic system; and

    (D)                report as Deficient deficiencies in:

    (i)                   water pressure and flow and operation of pressure switches;

    (ii)                 the condition of visible and accessible equipment and components; and

    (iii)                the well head, including improper site drainage and clearances.

    (10)             Specific limitations for private water wells.  The inspector is not required to:

    (A)                open, uncover, or remove the pump, heads, screens, lines, or other components or parts of the system;

    (B)                determine the reliability of the water supply or source; or

    (C)                locate or verify underground water leaks.

     

    (11)             Private sewage disposal (septic) systems.  The inspector shall:

    (A)                report:

    (i)                   the type of system;

    (ii)                 the location of the drain field; and

    (iii)                the proximity of any known water wells, underground cisterns, water supply lines, bodies of water, sharp slopes or breaks, easement lines, property lines, soil absorption systems, swimming pools, or sprinkler systems; and

    (B)                report as Deficient:

    (i)                   visual or olfactory evidence of effluent seepage or flow at the surface of the ground;

    (ii)                 inoperative aerators or dosing pumps; and

    (iii)                deficiencies in:

    (I)                  accessible or visible components;

    (II)                functional flow;

    (III)              site drainage and clearances around or adjacent to the system; and

    (IV)              the aerobic discharge system.

    (12)             Specific limitations for individual private sewage disposal (septic) systems.  The inspector is not required to:

    (A)                excavate or uncover the system or its components;

    (B)                determine the size, adequacy, or efficiency of the system; or

    (C)                determine the type of construction used.

     

    (13)             Whole-house vacuum system.  The inspector shall report as Deficient:

    (A)                inoperative units;

    (B)                deficiencies in the main unit; and

    (C)                deficiencies in outlets.

    (14)             Specific limitations for whole-house vacuum systems.  The inspector is not required to:

    (A)                inspect the attachments or hoses; or

    (B)                verify that accessory components are present.

     

    (15)             Other built-in appliances.  The inspector shall report deficiencies in condition or operation of other built-in appliances not listed in this section.

  •  

    Texas Administrative Code

     

     

    TITLE 22

    EXAMINING BOARDS

    PART 23

    TEXAS REAL ESTATE COMMISSION

    CHAPTER 535

    GENERAL PROVISIONS

    SUBCHAPTER R

    REAL ESTATE INSPECTORS

    RULE §535.227

    Standards of Practice: General Provisions

     


    (a) Definition of terms. The following words have the following meanings, unless the context clearly indicates otherwise.

      (1) Chapter 1102--Texas Occupations Code, Chapter 1102.

      (2) Functioning--Performing in an expected or required manner; carrying out the design purpose or intended operation of a part, system, component, member.

      (3) Inaccessible--Not having access without the use of special tools, equipment, or instruments, or removing doors, walls, stored items or similar obstructions, or by causing damage to a structure, finish or component, equipment or system, or by virtue of inadequate clearance, walkways, passageways, or hazardous condition.

      (4) In Need of Repair--Does not adequately function or perform.

      (5) Inspect--To look at and examine accessible items, parts, systems or components without, except as required by the rules of the Texas Real Estate Commission, laboratory, scientific or engineering evaluation or testing, destructive tests or the dismantling or removal of parts, members or components.

      (6) Inspector--A person licensed as a professional inspector, a person licensed as an apprentice inspector or a person licensed as a real estate inspector.

      (7) Performance--The act of carrying out, completing, executing or achievement of an operation, design or function in a manner consistent with the intent of the manufacturer, designer or accepted industry practice.

      (8) Report--A written or oral communication of the inspector's opinions, observations, determinations, and findings in an inspection.

      (9) Standards of Practice--§535.227 of this title (relating to Standards of Practice: General Provisions), §535.228 of this title (relating to Standards of Practice: Inspection Guidelines for Structural Systems, §535.229 of this title (relating to Standards of Practice: Inspection Guidelines for Mechanical Systems: Appliances, Cooling Systems, Heating Systems, Ducts, Vents and Flues, and Plumbing Systems), §535.230 of this title (relating to Standards of Practice: Inspection Guidelines for Electrical Systems) and §535.231 of this title (relating to Standards of Practice: Optional Systems).

    (b) Scope.

      (1) The standards of practice are the minimum levels of inspection practice required of inspectors for the accessible parts, components, and systems typically found in improvements to real property, excluding detached structures, decks, docks and fences. The inspector may provide a higher level of inspection performance than required by the standards of practice and may inspect parts, components, and systems in addition to those described by the standards of practice.

      (2) The inspector shall:

        (A) inspect items, parts, systems, components and conditions which are present and visible at the time of the inspection, but the inspector is not required to determine or estimate the remaining life expectancy or future performance of any inspected item, part, system or component;

        (B) operate mechanical and electrical equipment, systems, and appliances during an inspection in normal modes and operating range at the time of the inspection;

        (C) report which of the parts, components, and systems present in the property have or have not been inspected;

        (D) report as in need of repair inspected parts, components or systems that are not functioning or that the standards of practice require the inspector to report as in need of repair;

        (E) address all of the parts, components, and systems contained in the standards of practice in the property being inspected.

        (F) complete the standard inspection report form under §535.223 of this title (relating to Standard Inspection Reports) if that section applies;

        (G) identify in any written report the inspector who performed the inspection by name and license number;

        (H) comply with any other law or license requirement necessary to perform inspections or services other than what is required by the standards of practice, such as an air-conditioning and refrigeration contractor license which may be required for the inspector to make a direct in-line connection to a refrigerant system, or a structural pest control license which may be required to perform a wood-destroying-insect inspection;

      (3) In the event of a conflict between a specific provision and a general provision in the standards of practice, the specific provision controls. The standards of practice do not apply to the following:

        (A) parts, components or systems other than those specifically described;

        (B) conditions other than those specifically described, such as environmental conditions, presence of toxic or hazardous wastes or substances, presence of termites or other wood-destroying insects or organisms, compliance with codes, ordinances, statutes or restrictions or the efficiency, quality, durability of any item inspected;

        (C) any part, component or system the inspector excludes under the departure provision in this section; and

        (D) any determination of insurability or warrantability of any part, component or system.

    (c) Departure Provision.

      (1) An inspector shall exclude from the inspection any part, component or system which the inspector is not competent or qualified to inspect.

      (2) An inspector may exclude any part, component or system required for inspection by the standards of practice which is inaccessible, cannot be inspected due to circumstances beyond the control of the inspector, or the inspector's client has agreed is not to be inspected.

      (3) This departure provision does not prohibit an inspector from specializing nor require the inspector to specifically exclude other parts, components or systems not ordinarily considered a part of the inspector's specialty. However, the inspector shall comply with the standards of practice for the items being inspected.

      (4) If an inspector excludes any part, component or system listed in the standards of practice, other than one which the client has agreed is not to be inspected, the inspector shall:

        (A) advise the client at the earliest practicable time that the specific part, component or system will not be included in the inspection; and

        (B) state in any written inspection report that the excluded part, component or system was not inspected.

    (d) Enforcement. Failure to comply with §535.227 of this title (relating to Standards of Practice: General Provisions), §535.228 of this title (relating to Standards of Practice: Inspection Guidelines for Structural Systems, §535.229 of this title (relating to Standards of Practice: Inspection Guidelines for Mechanical Systems: Appliances, Cooling Systems, Heating Systems, Ducts, Vents and Flues, and Plumbing Systems), §535.230 of this title (relating to Standards of Practice: Inspection Guidelines for Electrical Systems) and §535.231 of this title (relating to Standards of Practice: Optional Systems) is a ground for disciplinary action as prescribed by Chapter 1102 and §535.224 of this title (relating to Proceedings before the Committee).

     

     

     

     

     

    RULE §535.228

     

     

     

     

    Standards of Practice: Inspection Guidelines for Structural Systems

     

    (a) Foundations. The inspector shall:

      (1) report the type of foundation (for example, slab-on-grade or pier and beam);

      (2) inspect the foundation, related structural components and/or slab surfaces;

      (3) inspect the crawl space area to determine the general condition of foundation components and report the method used to observe the crawl space if the inspector did not enter the crawl space because the space was inaccessible, hazardous conditions were present, or access or visibility was limited;

      (4) render a written opinion as to the performance of the foundation;

      (5) report general indications of foundation movement that are present and visible, such as sheetrock cracks, brick cracks, out-of-square door frames or floor slopes;

      (6) report as in need of repair any post tensioned cable ends that are not protected;

      (7) report as in need of repair a crawl space that does not appear to be adequately ventilated;

      (8) report as in need of repair conditions or symptoms that may indicate the possibility of water penetration that are present and visible, such as improper grading around foundation walls or plumbing leaks; and

      (9) report as in need of repair conditions that are present and visible and may be adversely affecting foundation performance, such as erosion or water ponding.

    (b) Specific limitations for foundations. The inspector is not required to enter a crawl space or any areas where headroom is less than 18 inches and the width of the access opening is less than two feet, or where the inspector reasonably determines conditions or materials are hazardous to health or safety of the inspector.

    (c) Interior walls, doors, ceilings and floors. The inspector shall:

      (1) report as in need of repair deficiencies of the surfaces of walls, ceilings and floors as related to structural performance or water penetration that are present and visible;

      (2) report as in need of repair accessible doors that do not operate properly, excluding locks and latches;

      (3) report as in need of repair deficiencies in steps, stairways, balconies and railings,

      (4) report as in need of repair spacings between intermediate balusters, spindles, or rails for steps, stairways, balconies, and railings that permit passage of an object greater than four inches in diameter; and

      (5) report as in need of repair the absence of safety glass in hazardous locations.

    (d) Specific limitations for Interior walls, doors, ceilings and floors. The inspector is not required to do the following:

      (1) determine the condition of floor, wall or ceiling coverings unless such conditions affect structural performance or indicate water penetration;

      (2) report obvious damage to floor, wall or ceiling coverings;

      (3) determine the condition of paints, stains and other surface coatings; or

      (4) determine condition of cabinets.

    (e) Exterior walls and doors, windows and door glazing. The inspector shall:

      (1) report as in need of repair present and visible deficiencies of exterior walls that are related to structural performance and water penetration;

      (2) report as in need of repair deficiencies in the condition and operation of exterior doors and garage doors, including door locks and latches when present.

      (3) report as in need of repair damaged glazing in windows and exterior doors;

      (4) report as in need of repair any insulated windows that are obviously fogged or display other evidence of broken seals;

      (5) report as in need of repair the absence of safety glass in hazardous locations;

      (6) report as in need of repair missing or damaged window and door screens;

      (7) report as in need of repair in homes having burglar bars the absence of functional keyless burglar bars in appropriate locations;

      (8) report as in need of repair inoperable windows at burglar bar locations of sleeping rooms or egress areas and any inoperable windows at other randomly sampled accessible burglar bar locations; and

      (9) report as in need of repair spacings between intermediate balusters, spindles and rails that permit passage of an object greater than four inches in diameter.

    (f) Specific limitations for exterior walls and doors, windows and door glazing. The inspector is not required to do the following:

      (1) report the condition or presence of storm windows or doors, awnings, shutters or security devices or systems;

      (2) determine the condition of paints stains or other surface coatings; or

      (3) determine the presence of, or extent or type of, insulation or vapor barriers in exterior walls.

    (g) Fireplace and chimney. The inspector shall:

      (1) report as in need of repair deficiencies in the visible components and structure of the chimney and fireplace;

      (2) inspect the interior of the firebox and the visible flue area, and report as in need of repair built up creosote in visible areas of the firebox and flue (the inspector is not required to determine the adequacy of the draft or perform a chimney smoke test);

      (3) report as in need of repair a damper that does not operate;

      (4) report as in need of repair the presence of non-combustible hearth extension;

      (5) report as in need of repair deficiencies in the lintel, hearth and material surrounding the fireplace, including clearances from combustible materials;

      (6) report as in need of repair the absence of firestopping at the attic penetration of the chimney flue, where accessible;

      (7) report as in need of repair any gas log lighter valves that do not function or leak gas;

      (8) report as in need of repair any circulating fan that does not operate, if present;

      (9) report as in need of repair deficiencies in combustion air vent, if present; and

      (10) report as in need of repair deficiencies in chimney coping or crown, caps or spark arrestor (inspected from ground level at a minimum).

    (h) Roof, roof structure and attic. The inspector shall:

      (1) report the type of roof covering and report as in need of repair:

        (A) a roof covering that is not appropriate for the slope of the roof;

        (B) fasteners that are not present or that are not appropriate, (where it can be reasonably determined); and

        (C) roof jacks, flashing and counter flashing that are not present or not properly installed.

      (2) inspect the general condition of, and report evidence of previous repairs to, flashing, skylights and other roof penetrations;

      (3) report as in need of repair inadequate attic space ventilation;

      (4) report as in need of repair deficiencies in the roof covering, structure and sheathing;

      (5) report any visible evidence of moisture penetration;

      (6) report as in need of repair the lack of or inappropriate installation of components such as purlins, struts, collar ties or rafter ties, where necessary;

      (7) report as in need of repair excessive deflections or depressions in the roof's surface relating to the performance of the framing and the roof deck;

      (8) enter and inspect attic space(s) except when inadequate access or hazardous conditions exist as reasonably determined by the inspector and report the method used to inspect the attic if the inspector did not enter the attic;

      (9) report the method used to inspect the roof if the inspection is performed from other than roof level;

      (10) inspect for the presence, and report the approximate depth of, insulation where visible; and

      (11) report as in need of repair deficiencies in visible installed gutter and downspout systems.

    (i) Specific limitations for roof, roof structure and attic. The inspector is not required to do the following:

      (1) determine the remaining life expectancy of the roof covering; or

      (2) inspect the roof from the roof level if the inspector reasonably determines that the inspector cannot safely reach or stay on the roof, or that damage to the roof or roof covering may result from walking on the roof.

    (j) Porches and decks. The inspector shall:

      (1) report as in need of repair structural deficiencies in porches, decks, steps, balconies and carports as to visible footings, joists, deckings, railings and attachment points, where applicable; and

      (2) report as in need of repair (except for decks which are not higher than 30 inches as measured from the adjacent grade) spacings between intermediate balusters, spindles or rails that permit passage of an object greater than four inches in diameter.

    (k) Specific limitations for porches and decks. The inspector is not required to inspect detached structures or waterfront structures and equipment, such as docks or piers.

     

    RULE §535.229

    Standards of Practice: Inspection Guidelines for Mechanical Systems: Appliances, Cooling Systems, Heating Systems, Ducts, Vents and Flues, and Plumbing Systems

     

    (a) Dishwasher. The inspector shall:

      (1) report as in need of repair any deficiencies in the door gasket, control knobs and interior parts, including the dish tray, rollers, spray arms and the soap dispenser;

      (2) report as in need of repair any interior signs of rust;

      (3) report as in need of repair a door spring that does not operate properly;

      (4) report as in need of repair deficiencies in the discharge hose or piping or the lack of back flow prevention;

      (5) report as in need of repair units that are not securely mounted;

      (6) report as in need of repair any water leaks;

      (7) inspect the unit's operation in normal mode with the soap dispenser closed; and

      (8) report as in need of repair spray arms that do not turn, soap dispensers that do not open or drying elements that do not operate.

    (b) Food waste disposer. The inspector shall:

      (1) report as in need of repair any deficiencies in the splash guard, grinding components, wiring and exterior;

      (2) report as in need of repair a unit that is not securely mounted; and

      (3) inspect the operation of the unit and report as in need of repair any unusual noise or vibration level and any signs of water leaks.

    (c) Range exhaust vent. The inspector shall:

      (1) report as in need of repair any deficiencies in the filter, vent pipe, light and switches;

      (2) inspect the operation of the blower and report as in need of repair any unusual sounds or vibration levels, or if the blower does not operate at all speeds;

      (3) report as in need of repair a vent pipe that does not terminate outside the structure when the unit is not of recirculating type or configuration.

      (4) report as in need of repair a vent pipe that is of inadequate material; and

      (5) report as in need of repair the absence of a range exhaust vent.

    (d) Electric or gas ranges. The inspector shall:

      (1) report as in need of repair broken or missing knobs, elements, drip pans or other parts, inadequate clearance from combustible material, or the absence of an anti-tip device;

      (2) report as in need of repair signal lights and elements or burners that do not operate at low and high settings;

      (3) report as in need of repair improper materials that are used for the gas branch line and the connection to the appliance; and

      (4) report as in need of repair the absence of a gas shut-off valve, or valve that is not properly located, is inaccessible, or leaks.

    (e) Electric or gas ovens. The inspector shall:

      (1) report as in need of repair any broken or missing knobs, handles, glass panels, door hinges, lights or light covers or other parts, or inadequate clearance from combustible material;

      (2) report as in need of repair deficiencies in the door gasket, tightness of closure and operation of the latch;

      (3) report as in need of repair an oven that is not securely mounted;

      (4) report as in need of repair heating elements and thermostat sensing elements that are not properly supported;

      (5) report as in need of repair deficiencies in the operation of the heating elements or the lighting, operation and condition of the flame;

      (6) report as in need of repair deficiencies in the operation of the clock and timer, thermostat and door springs; and

      (7) report as in need of repair any inaccuracy of the thermostat more than a 25 degree range plus or minus of a 350 degree setting, as measured by a thermometer.

    (f) Microwave oven. The inspector shall:

      (1) report as in need of repair any broken or missing knobs, handles, glass panels, or other parts, or a unit that is not securely mounted;

      (2) report as in need of repair any deficiencies in the door and seal (the inspector is not required to test for radiation);

      (3) report as in need of repair an oven that does not operate by heating a container of water or with other test equipment, as reasonably determined by the inspector; and

      (4) report as in need of repair a light that does not operate.

    (g) Trash compactor. The inspector shall:

      (1) inspect the overall condition of the unit;

      (2) report as in need of repair a unit that does not operate or operates with unusual noise or vibration levels; and

      (3) report as in need of repair a unit that is not securely mounted in place.

    (h) Other built-in appliances. The inspector shall report as in need of repair any deficiencies in condition or operation of other built-in appliances not listed in this section.

    (i) Bathroom exhaust vents and electric heaters. The inspector shall operate the unit, and report as in need of repair unusual sounds, speed and vibration levels or, when possible, vent pipes that do not terminate outside the structure.

    (j) Whole house vacuum system. The inspector shall:

      (1) inspect the condition of the main unit;

      (2) report as in need of repair a unit that does not operate; and

      (3) inspect the system from all accessible outlets throughout the house.

    (k) Water heaters. The inspector shall:

      (1) report the energy source;

      (2) inspect the unit and report as in need of repair fittings that leak or are corroded;

      (3) report as in need of repair temperature and pressure relief valve piping that lacks gravity drainage, is improperly sized (no smaller than the outlet fittings), has deficiencies in material, or lacks a correct termination;

      (4) report as in need of repair a temperature and pressure relief valve that does not operate when the valve is of an operable type and operation will not cause damage to persons or property as reasonably determined by the inspector (for example, it would be reasonable not to operate the valve if there is improper or undetermined termination of the drain pipe, a corroded or damaged valve, improper installation of valve or drain pipe, the drain pipe is of inappropriate material or there is no water supply cut-off valve at the unit);

      (5) report as in need of repair any broken or missing parts, covers or controls;

      (6) report as in need of repair deficiencies in the burner, flame and burner compartment, the operation of heating elements and the condition of wiring;

      (7) report as in need of repair deficiencies in materials used for the gas branch line and the connection to the appliance, the absence of a gas shut-off valve, or a valve that is not properly located, is inaccessible, or leaks;

      (8) if applicable, report as in need of repair deficiencies in the vent pipe, draft diverter, draft hood and their condition, draft, proximity to combustibles and vent termination point, observing for adequate combustion and draft air;

      (9) report as in need of repair the lack of a safety pan and drain (including the termination of the drain line) when applicable;

      (10) report as in need of repair an unsafe location or installation; and

      (11) inspect garage units or units which are located in rooms or enclosures opening into a garage and report as in need of repair the following:

        (A) a lack of protection for physical damage to the unit; and

        (B) burners, burner ignition devices or heating elements, switches or thermostats that are not a minimum of 18 inches above the lowest garage floor elevation.

    (l) Doorbell and chimes. The inspector shall:

      (1) inspect the condition of the unit and report as in need of repair a unit that does not operate; and

      (2) report as in need of repair any deficiencies in visible and accessible parts.

    (m) Attic power vents. The inspector shall:

      (1) report as in need of repair deficiencies in the operation and installation of the unit, including the wiring and mounting of the thermostat control, if so equipped and accessible; and

      (2) report as in need of repair unusual sounds or speed and vibration levels.

    (n) Garage door operator. The inspector shall:

      (1) report as in need of repair deficiencies in the installation, condition and operation of the garage door operator;

      (2) operate the door both manually and by an installed automatic door control;

      (3) report as in need of repair a door that does not automatically reverse during closing cycle, any installed electronic sensors that are not operable or not installed at the proper heights above the garage floor; and

      (4) report as in need of repair door locks or side ropes that have not been removed or disabled.

    (o) Hydrotherapy or whirlpool equipment. The inspector shall:

      (1) report as in need of repair a unit that does not operate, leaks, or is inaccessible;

      (2) report as in need of repair a unit that lacks a ground fault circuit interrupter or has an interrupter that does not operate;

      (3) report as in need of repair switches that are not in a safe location or do not operate;

      (4) report evidence of leaks under the tub if the access cover is available and accessible, reporting when the cover is absent or inaccessible (the inspector is not required to determine the adequacy of self-draining features of the circulation system); and

      (5) report as in need of repair deficiencies in the ports, valves, grates and covers.

    (p) Specific limitations for appliances. The inspector is not required to do the following:

      (1) operate or determine the condition of other auxiliary components of inspected items; or

      (2) inspect self-cleaning functions.

    (q) Cooling systems other than evaporative coolers. The inspector shall:

      (1) report the type of system and energy sources;

      (2) operate the system using normal control devices except when the outdoor temperature is less than 60 degrees Fahrenheit;

      (3) inspect for proper performance; such as by observing the temperature difference between the supply air and the return air or noticeable vibration of the blower fan and report as in need of repair any deficiencies;

      (4) report as in need of repair the lack of, or deficiencies in drainage of, condensate drain line and secondary drain line when applicable, including pipes made of inadequate material;

      (5) report as in need of repair a primary drain pipe that terminates in a sewer vent, if the termination is visible;

      (6) report as in need of repair a safety pan that is not appropriately sized for the evaporator coil or free of water or debris;

      (7) report as in need of repair a return chase and plenum that are not free of improper and hazardous conditions, such as gas pipes, sewer vents, refrigerant piping or electrical wiring.

      (8) report as in need of repair the lack of insulation on refrigerant pipes and the primary condensate drain pipe;

      (9) report as in need of repair a condensing unit that does not have adequate clearances, or air circulation, or that has deficiencies in the condition of fins, location, levelness and elevation above ground surfaces; and

      (10) report as in need of repair conductor sizing and over-current protective devices that are not appropriately sized for the unit.

    (r) Evaporative coolers. The inspector shall:

      (1) operate the motor and report as one or two speed;

      (2) observe the electrical pigtail connection at the motor

      (3) inspect the power source in the unit;

      (4) report as in need of repair a pump that does not function or deficiencies in the spider tubes, tube clips and bleeder system;

      (5) report as in need of repair deficiencies in the water supply line and float bracket;

      (6) report as in need of repair the absence of a minimum one-inch air gap between water discharge at float and water level;

      (7) report as in need of repair deficiencies in the fan (blower) and squirrel cage or rust build-up, deterioration or corrosion;

      (8) report as in need of repair deficiencies in the fan belt and pulleys;

      (9) report as in need of repair deficiencies in the housing side panels, the water trays, the exterior housing and the roof frame;

      (10) report as in need of repair deficiencies in the roof jack or other mounting point and the location of the seasonal damper at the unit; and

      (11) report as in need of repair deficiencies in the interior registers and the supply duct.

    (s) Specific limitations for cooling systems. The inspector is not required to do the following:

      (1) inspect for the pressure of the system coolant or determine the presence of leaks;

      (2) program digital-type thermostats or controls; or

      (3) operate setback features on thermostats or controls.

    (t) Heating systems. The inspector shall:

      (1) report the type of heating system and its energy sources;

      (2) report as in need of repair a system that does not operate properly using normal control devices;

      (3) report as in need of repair deficiencies in the controls and accessible operating components of the system;

      (4) in gas units, inspect the burner, and report as in need of repair deficiencies in the burner compartment, type, condition, draft and termination of the vent pipe, or proximity to combustibles; the lack of combustion and draft air or inappropriate location, or the lack of forced air in the burner compartment (full evaluation of the integrity of a heat exchanger requires dismantling of the furnace and is beyond the scope of a visual inspection);

      (5) report as in need of repair gas units that display flame impingement, uplifting flame, improper flame color or excessive scale buildup;

      (6) report as in need of repair gas units that use improper materials for the gas branch line and the connection to the appliance;

      (7) report as in need of repair in gas units deficiencies in materials used for the gas branch line and the connection to the appliance, the absence of a gas shut-off valve, or a valve that is not properly located, is inaccessible, or leaks; and

      (8) report as in need of repair elements in electric furnaces that do not operate;

      (9) report as in need of repair a return chase or plenum that are not free of improper and hazardous conditions, such as gas pipes, sewer vents, refrigerant piping or electrical wiring; and

      (10) report if the inspector deemed the furnace to be inaccessible.

    (u) Specific limitations for heating systems. The inspector is not required to do the following:

      (1) inspect accessories such as humidifiers, air purifiers, motorized dampers, heat reclaimers, electronic air filters or wood-burning stoves;

      (2) determine the efficiency or adequacy of a system;

      (3) program digital-type thermostats or controls; or

      (4) operate radiant heaters, steam heat systems or unvented gas-fired heating appliances.

    (v) Ducts, vents (including dryer vents) and flues. The inspector shall:

      (1) report as in need of repair deficiencies such as damaged ducting or insulation, improper material or improper routing of ducts where visible and accessible;

      (2) report as in need of repair the absence of air flow at all accessible supply registers in the habitable areas of the structure;

      (3) report as in need of repair deficiencies in accessible duct fans and filters;

      (4) report as in need of repair deficiencies in installation, such as gas piping, sewer vents, electrical wiring or junction boxes in the plenum, returns or chases or improper sealing, where visible;

      (5) report as in need of repair deficiencies in the flue system components;

      (6) report as in need of repair a flue or vent pipe that does not properly terminate; and

      (7) report as in need of repair deficiencies in materials used for the venting systems.

    (w) Specific limitations for ducts and vents. The inspector is not required to do the following:

      (1) determine the efficiency, adequacy or capacity of the systems;

      (2) determine the uniformity of the supply of conditioned air to the various parts of the structure;

      (3) determine the types of materials contained in insulation, wrapping of pipes, ducts, jackets, boilers and wiring;

      (4) operate venting systems unless ambient temperatures or other circumstances, in the reasonable opinion of the inspector, are conducive to safe operation without damage to the equipment; or

      (5) operate a unit outside its normal operating range as reasonably determined by the inspector.

    (x) Plumbing systems. The inspector shall:

      (1) inspect and report as in need of repair deficiencies in the type and condition of all accessible and visible water supply and waste-water and vent pipes;

      (2) inspect and report as in need of repair deficiencies in the operation of all fixtures and faucets where the flow end of the faucet is not connected to an appliance;

      (3) report as in need of repair the lack of back-flow devices, anti-siphon devices or systems or air gaps when applicable;

      (4) report as in need of repair incompatible materials in connecting devices between differing metals in the supply system, where visible;

      (5) report as in need of repair deficiencies in water supply by viewing functional flow in two fixtures operated simultaneously;

      (6) report as in need of repair deficiencies in functional drainage at accessible plumbing fixtures;

      (7) report as in need of repair deficiencies in installation and identification of hot and cold faucets;

      (8) report as in need of repair mechanical drainstops that are missing or do not operate if installed on sinks, lavatories and tubs;

      (9) report as in need of repair commodes that have cracks in the ceramic material, are improperly mounted on the floor, leak or have tank components which do not operate;

      (10) report as in need of repair accessible supply and drain pipes that leak;

      (11) report as in need of repair the lack of a visible vent pipe system to the exterior of the structure or improper routing or termination of the vent system;

      (12) report as in need of repair a shower enclosure that leaks; and

      (13) report as in need of repair any exterior faucet attached or immediately adjacent to the structure that does not operate properly.

    (y) Specific limitations for plumbing systems. The inspector is not required to do the following:

      (1) operate any main, branch or shut-off valves;

      (2) inspect any system that has been shut down or otherwise secured;

      (3) inspect any components that are not visible or accessible;

      (4) inspect any exterior plumbing components such as water mains, private sewer systems, water wells, sprinkler systems or swimming pools;

      (5) inspect fire sprinkler systems;

      (6) inspect or operate drain pumps or waste ejector pumps;

      (7) inspect the quality or the volume of well water;

      (8) determine the potability of any water supply;

      (9) inspect water-conditioning equipment, such as softeners or filter systems;

      (10) inspect solar water heating systems;

      (11) determine the effectiveness of anti-siphon devices on appropriate fixtures or systems;

      (12) operate free-standing appliances;

      (13) inspect private water supply systems, swimming pools, or pressure tanks;

      (14) inspect the gas supply system for leaks; or

      (15) inspect for sewer clean-outs.

     

     

    RULE §535.230

     

    Standards of Practice: Inspection Guidelines for Electrical Systems

     

    (a) Service entrance and panels. The inspector shall:

      (1) inspect service entrance cables and report as in need of repair deficiencies in the integrity of insulation, drip loop, separation of conductors at weatherheads and clearances;

      (2) report as in need of repair a drop, weatherhead or mast that is not securely fastened;

      (3) report as in need of repair the lack of a grounding electrode conductor in the service where visible, or the lack of secure connection to the grounding electrode or grounding system;

      (4) report as in need of repair accessible main or subpanels that are not secured to the structure or appropriate for their location (weather-tight if exposed to weather, appropriate clearances and accessibility), do not have inside covers (dead fronts) in place, do not have conductors protected from the edges of metal panel boxes, do not have trip ties installed on labeled 240 volt circuits, do not have proper fasteners or do not have knockouts filled;

      (5) inspect and report as in need of repair deficiencies in the type and condition of the wiring in the panels, in the compatibility of overcurrent protectors for the size of conductor being used and in sizing of listed equipment of overcurrent protection and conductors, when power requirements for listed equipment are readily available and breakers are labeled;

      (6) report as in need of repair a panel that is installed in a hazardous location, such as a clothes closet;

      (7) report as in need of repair the absence of appropriate connections, such as copper/aluminum approved devices, pig-tailed connections or crimp connections; and the absence of anti-oxidants on aluminum conductor terminations; and

      (8) report as in need of repair the lack of main disconnect(s).

    (b) Specific limitations for service entrance and panels. The inspector is not required to do the following:

      (1) determine service capacity amperage or voltage or the capacity of the electrical system relative to present or future use;

      (2) determine the insurability of the property;

      (3) conduct voltage drop calculations; or

      (4) determine the accuracy of breaker labeling.

    (c) Branch circuits, connected devices and fixtures. The inspector shall:

      (1) report the type of branch circuit wiring;

      (2) inspect all accessible receptacles and report as in need of repair a receptacle in which:

        (A) power is not present;

        (B) polarity is incorrect;

        (C) the unit is not grounded, if applicable;

        (D) there is evidence of arcing or excessive heat;

        (E) the unit is not secured to the wall;

        (F) the cover is not in place; or

        (G) ground fault circuit interrupter devices are not properly installed as set forth by the current edition of the National Electric Code, publication 70A of the National Fire Protection Association, or do not operate properly as shown by use of a separate testing device;

      (3) operate all accessible wall and appliance switches and report as in need of repair a switch that:

        (A) does not operate or is damaged;

        (B) displays evidence of arcing or excessive heat; or

        (C) is not fastened securely with cover in place.

      (4) inspect installed fixtures including lighting devices and ceiling fans;

      (5) report as in need of repair an inoperable or missing fixture;

      (6) report as in need of repair deficiencies in exposed wiring, wiring terminations, junctions and junction boxes;

      (7) report as in need of repair deficiencies or absences of conduit in appropriate locations or conduit that is not terminated securely;

      (8) report as in need of repair appliances and electrical gutters that do not have proper bonding;

      (9) report as in need of repair subpanels that are not properly bonded and grounded;

      (10) report as in need of repair the lack of disconnects in appropriate locations;

      (11) inspect (if branch circuit aluminum wiring is discovered in the main or subpanels) a random sampling of accessible receptacles and switches and report as in need of repair the absence of appropriate connections, such as copper/aluminum approved devices, pig-tailed connections or crimp connections;

      (12) report as in need of repair the improper use of extension cords; and

      (13) report as in need of repair the absence of, or deficiencies in, the installation and operation of smoke or fire detectors not connected to a central alarm system.